12v vs. 48v: Calculating the energy savings of OCP-style PSUs

25 May 18

Organizations like Open Compute Project (OCP) and Open19 have created open standards for alternatives to conventional server designs.

These architectures redefine how power is converted and distributed within an IT rack. Centralized rack-level power supply units (PSU) replace internal server power supplies.

12V has been the standard output for power supplies, but recently we’re seeing 48V, with claims of much higher overall efficiency.

Why 48V? It comes down to the quest for improved compute performance, which requires increasing the power to the chip, and at 12V, this isn’t practical.

I’ll explain why in another blog.

Efficiency: A Compare and Contrast Story

We thought it was important to research this topic to understand the expected efficiencies from the PSU to the server point of load (the components within the servers).

We created a model to illustrate the differences between the architectures, show the main drivers of the electrical losses, and see how varying parameters like redundancy of PSUs, oversizing of PSUs, and component efficiencies can impact the resulting overall efficiency.

The calculator allows you to analyze the power path efficiency of the different architectures, starting from the input power of the rack (PSU input), down to the voltage regulator modules (VRM) within the servers that deliver power to the individual server components.

Specifically, we looked at comparing conventional servers (PSUs within each server) and centralized rack-level PSUs, both 12V & 48V DC approaches.

With the default settings in our tool, the efficiency of the 12V rack level PSU architecture is 7 percentage points better than conventional servers (or 33% reduction in losses), and 48V is just over 1 percentage point better than 12V rack-level (7% reduction in losses).

So where does the efficiency improvement come from?

Redundancy - Centralizing PSUs to the rack allows for N+1 redundancy to be achieved for each rack, meaning there is one extra PSU per rack of servers (i.e. 5+1) rather than one extra for every server (1+1) which is typical for conventional servers.

This reduction in power converting components increases the overall efficiency of the system.

Oversizing - Conventional PSUs tend to have an oversizing factor between 2x and 3x, whereas a consolidated rack-level PSU will have less oversizing (we assume 1.2).

More efficient components - The most common grade of PSU used in data centers is 80 Plus Silver standard, which has a max efficiency of 88%.

In comparison, data shows 94% and 95% max efficiencies for 12V and 48V rack-level PSUs, respectively (based on data from General Electric). There is also likely to be an efficiency improvement in the VRM when the conversion occurs at 48V instead of 12V.

Findings from the Expert

Here are what I believe the key takeaways are from this analysis:

  • Rack-level architectures do show significant improvement in efficiency over conventional servers, primarily due to the reduction in oversizing of the PSUs (both from less redundancy “overhead” and consolidation of server PSUs).
  • 48V direct current is a likely bet for the future, not for the incremental efficiency improvement over 12V direct current, but because of the need for increased compute and density.

What do you think?

Article by Wendy Torell, Schneider Electric blog network. 

Gartner names LogRhythm leader in SIEM solutions
Security teams increasingly need end-to-end SIEM solutions with native options for host- and network-level monitoring.
Cylance makes APIs available in endpoint detection offering
Extensive APIs enable security teams to more efficiently view, enrich, and contextualise real-time intelligence collected at the endpoint to keep systems secure.
NBN Co rolls out 'optimised' wholesale business bundles for ISPs
“We recognise some businesses are on nbn powered plans that have not been optimised for their needs," says Paul Tyler.
How Schneider Electric aims to simplify IT management
With IT Expert, Schneider Electric aims to ensure secure, vendor agnostic, wherever-you-go monitoring and visibility of all IoT-enabled physical infrastructure assets.
SolarWinds adds SDN monitoring support to network management portfolio
SolarWinds announced a broad refresh to its network management portfolio, as well as key enhancements to the Orion Platform. 
Preparing for the future of work – growing big ideas from small spaces
We’ve all seen it: our offices are changing from the traditional four walls - to no walls. A need to reduce real estate costs is a key driver, as is enabling a more diverse and agile workforce.
JASK prepares for global rollout of their AI-powered ASOC platform
The JASK ASOC platform automates alert investigations, supposedly freeing the SOC analyst to do what machines can’t. 
Pitfalls to avoid when configuring cloud firewalls
Flexibility and granularity of security controls is good but can still represent a risk for new cloud adopters that don’t recognise some of the configuration pitfalls.